Fault Diagnosis

Release 04/02

6-8

Panel PC 670 Computing Unit, Equipment Manual

6.8

Computing Unit Self-Test Prior to Booting

After switching on the SIMATIC PC a self-test is initiated (POST = Power On Self
Test). If errors are detected during the POST, the corresponding sequence of
POST beeps (beep code) are issued. Each beep code consists of 2 x 2
sequences.

In addition, the individual test steps which the self-test executes, are issued on the
I/O port 80h.

Conversion table for the beep codes to hexadecimal representation:

Beeps

Hex Code

B

B

0

B

BB

1

B

BBB

2

B

BBBB

3

BB

B

4

BB

BB

5

BB

BBB

6

BB

BBBB

7

BBB

B

8

BBB

BB

9

BBB

BBB

A

BBB

BBBB

B

BBBB

B

C

BBBB

BB

D

BBBB

BBB

E

BBBB

BBBB

F

Example

B

BBB

BBB

B

Beeps

2

8

Hex Code

Test system memory

Meaning

Special codes

In addition to the beep codes listed below, there are also special codes:

3x short

INSERT button has been pressed during the system start:
The Onboard Device Installation is skipped. The Onboard
Graphic is used as the standard output.

1x long 8x short

Fault reading the MPI system information:
Contact your technical service department.

4x short

MPI EPROM was programmed for the first time.

1x long 5x short

Ethernet error: Contact your technical service department.