beautypg.com

Blocked air intake, Fault messages – State Industries SHE50-100PE User Manual

Page 63

background image

61

Servicing should only be performed by a Qualified Service Agent

fault messages

displayed message/condition/indicates

possible causes - checK/repair

blocked air intake

The Control System has detected the Blocked Intake Air

switch has open contacts - restricted combustion air intake

to the water heater, inadequate supply of combustion air.

CHANGE

BACK

ADVANCED

Blocked Air Intake

Fault occurred 2 mins ago

The combustion air intake is

restricted.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

Important Service Reminder:

When performing any troubleshooting steps outlined in

this manual always consider the wiring and connectors

between components. Perform a close visual inspection

of all wiring and connectors to a given component before

replacement.

• If the water heater has been installed as a

conventional vent appliance - Ensure screen inside

the intake air connection fitting is not clogged with

debris. Clear any debris from the screen. See Intake

Air Connection on page 5.

• If water heater has been installed in a direct Vent

configuration - check for restrictions, intake air

pipe size too small, too many equivalent feet, or

too many installed elbows in the intake air piping.

Review venting installation section of the Instruction

Manual that came with the water heater - see Table

1 on page 4 in this manual. Ensure the vent/intake

air piping has been installed within manufacturers

requirements.

• If water heater has been installed in a direct Vent

configuration - ensure there is not a low point in the

intake air piping that will allow water/condensate to

collect and block the intake air piping.

• If water heater has been installed in a direct Vent

configuration - temporarily disconnect the intake

air pipe to the water heater - ensure the screen

inside the intake air connection was removed during

installation. See Intake Air Connection on page 5.

• Check all wiring between the Blocked Intake Air

switch and the CCB’s J6 Socket (page 41) pins 4 &

14. Perform close visual inspection of the pins inside

the plug and socket - ensure plugs and sockets are

mating properly and providing good contact. Repair/

replace anything worn or damaged.

• If water heater has been installed in a direct Vent

configuration - ensure the screen inside the intake air

pipe termination fitting is not blocked or restricted.

Perform the Pressure Switch Tests on page 31.

Replace the Blocked Intake Air switch if it is defective.

• Call the toll free support phone number on the back

cover of this manual for further assistance if the

problem has not been corrected after performing the

procedures outlined here.

This manual is related to the following products: