Heater status – State Industries SHE50-100PE User Manual

Page 52

background image

50

Servicing should only be performed by a Qualified Service Agent

temperatures menu

description/action

display

Tank Temperature - non adjustable - Control System

sensed temperature from the Temperature Probe.

Tank Probe offset - adjustable user setting, range -5° to

+5° (factory setting 0°).
The Tank Probe offset is used to calibrate Control System

temperature sensing. This can improve the precision of

temperature control in the storage tank and at points of use.

This feature can also be used to compensate for building

recirculation loops (hot water returning to the storage tank)

that may cause the heating cycles to terminate prematurely.
Example: If the current sensed temperature from the

temperature probe is 120°F (49°C) and the offset setting for

the probe is adjusted to a value other than 0°, the Control

System would calibrate or “offset” the sensed temperature

from the probe. Heating cycles would be activated and

deactivated based on the calibrated (offset) temperature.
note: The Tank Probe offset should only be used if the hot

water supply temperature varies greatly from the operating

Set Point setting. These settings are adjusted in the same

way described for the operating Set Point And differential

Adjustment on page 49.

Operating Set Point

140°F

Differential

8°F

Tank Temperature

120°F

Tank Probe Offset

0°F

CHANGE

BACK

HELP

Temperatures

heater status

description/action

display

Select Heater Status from the Main Menu and press the

operational Button under "SELECT" to enter this menu. This

menu contains non adjustable operational information. use the

up & down Buttons to navigate the menu.

Status - displays the current operating State, see Table 6

on page 48 for a description of the various operational states.

eco contact, blocked inlet ps, Blocked outlet PS,

blower prover ps - displays the current state of the switch

contacts; open or closed.

blower low on, blower high on - displays whether

the Combustion Blower is running at high speed during

Pre/Post purge and the Heating operating states or the

Combustion Blower is running at low speed during the

Igniter Warm up operating state; yes = blower is running

at the designated speed, no = blower is not running at the

designated speed.

igniter on, Gas Valve on - displays whether or not the

Control System is currently energizing these water heater

components; yes = energized, no = de-energized.

Igniter Current - displays whether or not the Control

System has detected the required minimum current.

Flame Detected - displays whether or not the Control

System has detected flame at the Burner during ignition

from the Flame Sensor.

External Input Enable - displays whether or not the S1

dipswitches have been configured to activate the Enable/

disable circuit; yes = the Enable/disable circuit has been

activated, no = the Enable/disable circuit has not been

activated. The factory setting is "no" or deactivated.

Ignition Trials - displays whether or not the S1 dipswitches

have been configured to allow 1 or 3 trials for ignition

before declaring an Ignition Failure Fault condition. The

factory setting is for 3 trials.

Top of Menu

Status

Standby

ECO Contact

Closed

Blocked Inlet PS

Closed

Blocked Outlet PS

Closed

Blower Prover PS

Open

Blower Low On

No

Blower High On

No

BACK

HELP

Heater Status

Bottom of Menu

Blower High On

No

Igniter On

No

Igniter Current

No

Gas Valve On

No

Flame Detected

No

External Input Enable

No

Ignition Trials

3

BACK

HELP

Heater Status