beautypg.com

State Industries SHE50-100PE User Manual

Page 32

background image

30

Servicing should only be performed by a Qualified Service Agent

Sensing Tubes
The three pressure switches monitor pressure through plastic sensing tubes from three different sensing

ports on the water heater, see Figure 32 below.
The Blower Prover switch monitors pressure from the Combustion Blower's outlet, see Figure 14 on page 15.

The Blocked Intake Air switch monitors pressure from the Combustion Blower’s intake air connection fitting,

see Figure 1 on page 5. The Blocked Exhaust switch monitors pressure from the exhaust elbow on the bottom

of the water heater; there is an aluminum connecting tube mounted on the side of the water heater between

the Blocked Exhaust switch at the top and the exhaust elbow at the bottom. Two short pieces of plastic

sensing tube are used at either end of this aluminum tube to connect to the pressure switch and the exhaust

elbow, see Figure 3 on page 8.
These plastic sensing tubes must be routed to the correct sensing ports on the water heater. Sensing tube

routing should always be checked whenever Blower Prover Open, Blower Prover Failure, Blocked Air

Intake or Blocked Exhaust is displayed on the Control System LCd, see Figure 31 on page 29. These "Fault

Conditions" can be caused by incorrect sensing tube routing.

BLOWER PROVER

BLOCKED INTAKE AIR

PRESSURE SWITCH SENSING TUBE CONNECTIONS

BLOCKED EXHAUST

BLOCKED EXHAUST

Figure 32

This manual is related to the following products: