Servicing should only be performed by a Qualified Service Agent

venturi

A Venturi is mounted on the inlet of the Combustion Blower. All combustion air flows through the Venturi. The

outlet of the 24 Volt Gas Valve connects directly to the side of the Venturi. Fuel gas flows from the outlet of

the 24 Volt Gas Valve into the side of the Venturi directly.
Inside the Venturi there is a cone shaped restrictor that constricts the air passage to the Combustion Blower

inlet. As air enters the constriction point it’s velocity increases. A pressure drop occurs at this point and

creates a negative pressure in the cavity between the cone shaped restrictor and the Venturi housing. This

negative pressure “pulls” gas from the outlet of the 24 Volt Gas Valve into the Combustion Blower where it is

mixed with combustion air and then supplied to the Burner. See Figure 22 below.
This gas feed system does not produce a typical manifold gas pressure to the Burner. The manifold (offset)

gas pressure, gas pressure to the Burner, is very low. See Gas Pressure on page 25.

Negative Pressure

Negative Pressure

Velocity Increases

At Constriction Point

Pressure Drops

GAS VAL

VE

Combustion Air

VENTURI

VENTURI INLET

GAS INLET

24 VOLT GAS VALVE

BLOWER

BLOWER

SUPPLY GAS

BURNER

Figure 22