2] in the case of a master station, 1] flag table -2, 3 [2] in the case of a master station – Sharp JW-21MN User Manual

Page 84

background image

12-3

[2] In the case of a master station

(1) Communication monitor flag

This flag is used to monitor the communication condition with other stations. Non-connected station
keeps this flag as "OFF."

The master station periodically executes communication recovery operation with the communication
error slave station. When the error situation is recovered, the master station returns to normal
communication.

(2) Operation condition monitor flag [1]

This flag is used to monitor the operation condition of slave stations when the communication with
each slave station is normal.
Non-connected station keeps this flag as "OFF."

* Even if a master station PC has stopped operation normally or by an error, the JW-21MN turns

"ON" this flag while communicating.

(3) Operation condition monitor flag [2]

This flag is used to monitor the abnormal stop of each slave station when the communication with
each slave station is normal.
Non-connected station keeps this flag as "OFF."

* Even if a master station PC has stopped operation normally or by an error, the JW-21MN turns

"ON" this flag while communicating.

Flag

Improper setting of parameter, BCC check error, or other errors.

When the parameter address 007777

(8)

of the master station is set to "00

(H)

."

Condition for flag operation

Own

station

flag

(master

station)

When the parameter address 007777

(8)

of the master station is set to "01

(H)

,"

and the master station is operating normally.

Flag operation

ON

OFF

Communication monitor flag (1) of the master
station is turned "OFF."

Flag

Condition for flag operation

Flag operation

Other

station’s

flag

(01 to 77)

Stopped communication or unable to
communicate with slave stations.

Specific

slave

station

All slave stations

ON

Normal communication with slave stations.

OFF

Slave station that communication monitor flag (1) is
turned to "OFF."

Flag operation

Condition for flag operation

Flag

Not specified

Own

station flag

(master

station)

Communication monitor flag (1) of the master station is turned "OFF."

Communication monitor flag (1) of the master station is turned "ON."

All slave

stations

Specific

slave

station

Flag operation

Other

station’s

flag

(01 to 77)

OFF

Flag

Condition for flag operation

Communication monitor flag (1) of the master station
is turned "OFF."

Each slave station is normal.
Any of the slave stations is faulty (caused to be
stopped abnormally).

ON

ON

OFF

Flag

Flag operation

Condition for flag operation

Slave station that communication monitor flag (1)
is turned to "OFF."

Communication monitor flag (1) of the master station is turned "ON."

Communication monitor flag (1) of the master station is turned "OFF."

Own

station flag

(master

station)

Other

station’s

flag

(01 to 77)

Flag

Condition for flag operation

Slave station stops operation (not by an error cause).

Specific

slave

station

All slave stations

Not specified

OFF

ON

Slave station is operating.

Communication monitor flag (1) of the master
station is turned "OFF."

Flag operation

ON

OFF