beautypg.com

Sharp JW-21MN User Manual

Page 11

background image

2-2

Communication cables should be laid from the master station to the slave station one by one.
Multiple wiring from one point or wiring without terminators may cause communication errors.

Arrange total cable length within 1 km.

Arrange branch cable line from a trunk within 400 mm.

Prior to any electric welding around the JW-21MN, take out the coaxial cable from the JW-21MN.
While the coaxial cable is connected to the JW-21MN, any electric welding nearby the JW-21MN
will cause the welding current to enter the JW-21MN and may damage part of its circuit pattern.

Coaxial cable

JW-21MN

JW-21MN

Turn

"

ON

"

shield ground switch

Electric welder

Note: In case enough conductivity is not

established.

Wraparound current

Rack etc.

Turn

"

ON

"

shield ground switch

(Note)

Joint using a
connector