13] read the optional parameters, 14] set the optional parameters, 13] read the optional parameters -10 – Sharp JW-21MN User Manual
Page 49: 14] set the optional parameters -10
10-10
[13] Read the optional parameters
Read the parameter data for option module (other than JW-21MN) from the control module.
[Write mode assignment]: None
[Communication format]
Command
Response
[Ex.] Read the parameters at address 030 to 032
(8)
for an option module (No.3). (Data in frames are in
hexadecimal, except when followed by an
(8)
, indicating octal data).
Command
Response
[14] Set the optional parameters
Write parameter data of option module (other than JW-21MN) to the control module.
[Write mode assignment]
2 (or when the PC is stopped by using a "PC operation stop F8
(H)
" command).
[Communication format]
Command
Response
[Ex.] Write 14
(H)
, 00
(H)
, and 33
(H)
to parameter address 040 to 042
(8)
in option module (module No. 2).
(The data in cells are in hexadecimal, except when followed by an
(8)
,indicating octal data.)
Command
Response
"+"
"C"
"L"
"A"
CMD SUB
ATTR UNO PAADR
N
"+"
ACK
"C"
"L"
"A"
CMD
SUB ATTR UNO PAADR
N
D1
DN
2B
43
4C
41
42
02
00
03
030
(8)
003
(8)
"+"
"C"
"L"
"A"
CMD
SUB ATTR UNO PAADR N
2B
00
43
4C
41
42
02
00
03
030
(3)
003
(3)
15
21
03
ACK
CMD
SUB
030
031
032
Read out data
"+"
"C"
"L"
"A"
CMD SUB
ATTR UNO PAADR
N
D1
DN
"+"
ACK
"C"
"L"
"A"
CMD
SUB ATTR UNO PAADR
N
2B
00
43
4C
41
42
12
00
02
040
(8)
003
(8)
ACK
CMD
SUB
2B
43
4C
41
42
12
00
02
040
(8)
003
(8)
14
00
33
"+"
"C"
"L"
"A"
CMD SUB ATTR UNO PAADR N
040
041
042
Read out data
(Symbols other
than the left: See
page 10-3.)
Symbol
Data
Details
CMD
42
(H)
Function code
SUB
02
(H)
Sub code
UNO
00 to 07
(H)
Set value for the module No. switch
PAADR
000 to 077
(8)
Read the starting address
N
01 to 40
(H)
Number of bytes to read out
D1 to DN
See the example Read out data (for number of bytes of reading data)
(Symbols other
than the left: See
page 10-3.)
Symbol
Data
Details
CMD
42
(H)
Function code
SUB
12
(H)
Sub code
UNO
00 to 07
(H)
Set value for the module No. switch
PAADR
000 to 077
(8)
Write the starting address
N
01 to 40
(H)
Number of bytes to write
D1 to DN
See the example
Write data (corresponding to the number of bytes
to write)