AERCO RECON 1000 User Manual
Page 97
RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 6 – MAINTENANCE
OMM-0103_0A
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
Page 97 of 178
GF-147
Phone: 800-526-0288 PRI:
10/28/2014
LWCO Capacitor Integrity Test – Continued
5. Confirm that the ohmmeter does NOT read a short.
NOTE
If the ohmmeter reads a short, the capacitor assembly needs to be replaced.
Refer to document TID-0094, provided with the 24-month maintenance kit,
for LWCO replacement instructions.
6. Remove both ohmmeter probes and reconnect the Shell Harness connector to the P5
connector on the rear of the C-More controller.
6.11.2 Low Water Cutoff (LWCO) - Standard C-More Test
Perform the standard Low Water Cutoff test using the C-More controls as described below.
Standard Low Water Cutoff C-More Test
1. Turn on the AC power to the unit.
2. Press the TEST switch on the C-More controller and confirm that the blinking "Low Water
Level" message appears on the C-More display within 4 seconds.
3. Press the RESET key, followed by the Clear button, and confirm that the "Low Water
Level" message is cleared.