CHAPTER 3 – OPERATION
Page 48 of 178
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
OMM-0103_0A
PRI: 10/28/2014
Phone: 800-526-0288
GF-147
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
24 Temp
Gov
Enable or Disable
Enable
25 GOV
Limit-5
0 100
30
26 GOV
Limit-7
0 100
20
27 GOV
Limit-10
0 100
15
28 GOV
Limit-12
0 100
10
29 GOV
Limit-15
0 100
5
30 PID
Output
0%
100%
Read Only Value
31 P
Output
0%
100%
Read Only Value
32 I
Output
0%
100%
Read Only Value
33 D
Output
0%
100%
Read Only Value
34 Reset
Defaults
Yes No
No
3.8 CALIBRATION MENU
The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed below.
A full description of each item appears in Table A-5 of Appendix A – Recon Menu Item
Descriptions.
Table 3-6: Calibration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1 Stepper
Fbk
Cal 0%
Cal 100%
Verify 50%
Cal 0%
2
Purge Timer
5 sec.
60 sec
Depends on unit type/size
3
Post Purge Timer
0 sec.
60 sec.
0 sec.
4
IGN Position
5%
60%
Depends on unit type/size
5
FFWD Temp Disply
Enabled or Disabled
6
Outlet Tmp Dsply
Enabled or Disabled
7
Inlet Tmp Dsply
Enabled or Disabled
8
Valv Pos Out Dsp
Enabled or Disabled
9
Exhaust Tmp Dsp
Enabled or Disabled
10 VP Up Rate
0.5
60.0
Depends on unit type/size
11 VP Down Rate
0.5
60.0
Depends on unit type/size
12 Purge Blwr Offst
-1.0
8.0
Depends on unit type/size