AERCO RECON 1000 User Manual
Page 46
RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
Page 46 of 178
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
OMM-0103_0A
PRI: 10/28/2014
Phone: 800-526-0288
GF-147
Table 3-4: Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
2
Unit Type
RECON WtrHeater
RECON WtrHeater
3
Unit Size
500 MBH, 1000 MBH
500 MBH
4
Fuel Type
Natural Gas, Propane
Natural Gas
5
Water Heater Mode
Constant Setpoint, Remote
Setpoint,
Constant Setpoint
6
Remote Signal
(If Mode = Remote Setpoint,
Direct Drive or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS)
Network
4 – 20 mA,
1-5V
7
Outdoor Sensor
Enabled or Disabled
Disabled
8
System Start Tmp
(If Outdoor Sensor = Enabled)
30°F 100°F 60°F
9
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
10
Setpt Hi Limit
Setpt Lo Limit
190°F
150°F
11
Temp Hi Limit
40°F
200°F
160°F
12
Max Valve Position
40%
100%
100%
13
Pump Delay Timer
0 min.
30 min.
0 min.
14
Aux Start On Dly
0 sec.
120 sec.
0 sec.
15
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
16
* Analog Output
Off, Setpoint, Outlet Temp, Valve
Pos 4-20mA, valve Pos 0-10v
* Valve Pos 0-10v
17
Low Fire Timer
2 sec.
600 sec.
2 sec.
18
Setpt Limiting
Enabled or Disabled
Disabled
19
Setpt Limit Band
0°F
10°F
5°F
20
Network Timeout
5 Sec
999 Sec
30 Sec
21 Shutoff
Dly
Temp
0
25
8
22 Demand
Offset
0
25
5
23
Deadband High
0
25
0
24 Deadband
Low
0
25
0
25
IGST Version
V2.00 or Lower
V2.02
0
26
IGN Timing Setting
4 Sec
7 Sec
-
-WARNING! -
* DO NOT CHANGE the Analog Output menu item from its
default setting (Valve Position 0-10V).