RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0103_0A
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
Page 45 of 178
GF-147
Phone: 800-526-0288 PRI:
10/28/2014
3.5 SETUP MENU
The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour, requiring the correct password to be reentered when required.
In addition, the Setup Menu is also used to enter date and time, and units of temperature
measurements. A view-only software version display is also provided to indicate the current
Control Box software version.
A full description of each item appears in Table A-2 of Appendix A – Recon Menu Item
Descriptions.
Table 3-3: Setup Menu
Menu Item
Display
Available Choices or Limits
Default
Minimum
Maximum
1 Password
0
9999
0
2 Language
English
English
3
Time
12:00 am
11:59 pm
4 Date
01/01/00
12/31/99
5
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
6 Comm
Address
0
127
0
7
Baud Rate
2400, 4800, 9600, 19.2K
9600
8
OnAER Mode
Ethernet Or SD Card
Ethernet
9
Min Upload Timer
0
9999 Sec
0
10
Unit Alpha
E, G, H, R, N or A
A
11
Unit Year
0
99
0
12
Unit Serial #
0
9999
0
13
Software
Ver 0.00
Ver 9.99
Current software
version
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for
operation in the Constant Setpoint mode. The remaining options in this menu require the valid
password to be entered, prior to changing existing entries. This menu contains a number of
other configuration settings which may or may not be displayed, depending on the current
operating mode setting.
A full description of each item appears in Table A-3 of Appendix A – Recon Menu Item
Descriptions.
NOTE
The Configuration Menu settings shown in the table below are
Factory-Set in accordance with the requirements specified for
each individual order. Therefore, under normal operating
conditions, no changes will be required.