AERCO RECON 1000 User Manual
Page 47
RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0103_0A
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
Page 47 of 178
GF-147
Phone: 800-526-0288 PRI:
10/28/2014
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by Factory-Trained personnel.
A full description of each item appears in Table A-4 of Appendix A – Recon Menu Item
Descriptions.
Table 3-5: Tuning Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Prop Band
1°F
200°F
30°F
2
Integral Gain
0.00
10.00
3.00
3
Derivative Time
0.00 min
2.00 min
0.20 min
4
Min Load Adj
-50°F
+50°F
0°F
5
Max Load Adj
-50°F
+50°F
0°F
6
FFWD Temp
30°F
245°F
Read Only Value
7
Outlet Feedback
Yes (On) or No (Off)
Yes (On)
8 Feedback
Gain
0.01
1.00
0.10
Breakpoints – shown only if the Calibration Menu item (see section 3-8) Heatr Bkpt Dsp =
Enabled. The Breakpoint values correspond to a 130°F default setpoint
9
Breakpt at 100%
30°F
240°F
85°F
10
Breakpt at 90%
30°F
240°F
86°F
11
Breakpt at 80%
30°F
240°F
87°F
12
Breakpt at 70%
30°F
240°F
88°F
13
Breakpt at 60%
30°F
240°F
89°F
14
Breakpt at 50%
30°F
240°F
90°F
15
Breakpt at 40%
30°F
240°F
94°F
16
Breakpt at 30%
30°F
240°F
103°F
17
Breakpt at 20%
30°F
240°F
118°F
18
Breakpt at 10%
30°F
240°F
134°F
19
Breakpt at 0%
30°F
240°F
136°F
WHM Items – the remaining items below appear only if WHM is enabled:
20 FDback Start Pos
0% 100%
30%
21 Fdback End Pos
0% 100%
60%
22 Max
Feedback
0% 100%
30%
23 Fdback
Value
0%
100%
Read Only Value