RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 8 – WATER HEATER MANAGEMENT

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 127 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

8.8.3 Control and Power Wiring

Control and power wiring connections to the sequencing valves associated with each C-More
WHM unit is accomplished by simply ensuring that the 4-pin Molex connectors on the units are
connected to the corresponding connectors on the valves.

Figure 8-4 WHMS Network Wiring Diagram

NOTES:

Wiring to be shielded twisted-
pair cable (Belden 9841 or
equivalent).

Complete the following
instructions:
1. Activate DIP 1 (Modbus

TERM) on the first and last
units in the daisy chain.

2. Tie incoming/outgoing

shields together and
terminate at the shield
terminal of the LAST WHMS
slave in the chain.

3. On the CPU board inside the

C-More Control Panel of the
last unit on the chain, turn
the DIP switches labeled
BIAS1 and BIAS2 to the
“ON” position.