CHAPTER 6: MAINTENANCE
6.1 MAINTENANCE SCHEDULE
The RECON Water Heater requires regular routine maintenance to ensure continued reliable
operation throughout the service life of the unit. For optimum operation, AERCO recommends
that the following routine maintenance procedures be performed in the time periods specified in
Table 6-1.
Appendix I contains a list of the recommended spare parts for maintenance of RECON units.
--WARNING! -
To avoid personal injury, prior to servicing ensure that the following
guidelines are strictly observed:
Disconnect the AC supply by turning off the service switch and
AC supply circuit breaker.
Shut off the gas supply at the manual shut-off valve provided with
the Unit
Allow the Unit to cool to a safe water temperature to prevent
burning or scalding
Table 6-1: Maintenance Schedule
Section
Item
6 Mos.
12 Mos.
24 Mos.
Labor
Time
6.2
Igniter-Injector
(58023)
* Inspect
* Inspect
Replace
15 min.
6.3
Flame Detector
(kit # 24356-2)
* Inspect
* Inspect
Replace
15 min.
6.4
Combustion
Calibration
* Check
Check
1 hr.
6.5
Testing of
Safety Devices
Test
20
min.
6.6
Fireside
Inspection
Inspect &
Clean
2 hrs.
6.7
Waterside
Inspection
* Inspect
Inspect
1 hr.
6.8
Heat Exchanger
Cleaning
Inspect & Clean
(as required)
2 hrs.
6.9
Condensate
Drain Trap
Inspect
Inspect & Clean
30 min.
6.10
Air Filter
(59139)
* Inspect
* Inspect
Replace
5 min.
*
Replace as necessary.