RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 2 – INSTALLATION
OMM-0103_0A
AERCO International, Inc.
100 Oritani Dr. Blauvelt, NY 10913
Page 23 of 178
GF-147
Phone: 800-526-0288 PRI:
10/28/2014
2.6 INSTALLING THE TEST HOSE BIB AND DRAIN VALVE
A Test Hose Bib must be installed upstream of the hot water outlet shut off valve, This is
required for startup and testing (see Figure 2-5 A). The pipe diameter should be a minimum of
3/4". The Test Hose Bib cannot be omitted.
Figure 2-5 A: Test Hose Bib Location – Left Side View
The drain valve, which is shipped loose, must be installed on the cold water inlet. It is suggested
that it be installed on the right side of the unit, on a nipple attached to the building recirculation
inlet (see Figure 2-5 B), with a cap on the end. It could instead be installed on the cold water
inlet pipe, on the left side of the unit.
Figure 2-5 B: Drain Valve Location – Right Side View
TO DRAIN
TEST
HOSE BIB
HOT
WATER
OUT
TEST HOSE BIB
CONNECTION
HOT WATER SHUTOFF VALVE
BUILDING
RECIRCULATION
INLET
COLD
WATER
INLET
DRAIN VALVE
NIPPLE AND CAP