beautypg.com

Fill-Rite 300V Series Fuel Transfer Pump User Manual

Page 4

background image

4

CAUTION! A pressure retaining fill cap can be used to reduce fuel loss through
evaporation, but note that it may reduce the flow rate.

WARNING! Installations must comply with all local, state, and national fire
codes, as appropriate to the intended use of the pump.



Typical Skid Tank Installation


Materials:

1-

1/4” pipe cut to a length that

will terminate at least

3” from the

bottom of the tank when installed
into the tank adapter with the
tank adapter installed into the
tank flange (see SKID TANK
INSTALLATION
diagram).

Threaded pipe joint sealant
appropriate for application.

Installation Procedure:

1)

Thread the 1-

1/4” pipe into the

tank adapter. Seal threads liquid
tight with appropriate thread
sealant.

2)

Install the tank adapter into the
tank flange; seal threads liquid
tight with appropriate thread
sealant.

3)

Mount the pump on the adapter;
seal threads liquid tight with
appropriate thread sealant.

4)

Fill-Rite recommends installation
of our Anti-Siphon Device (see
page 7 for detailed information).

CAUTION! Do not use additional check valves or foot valves unless they have a
proper pressure relief valve built into them. Note that additional check valves will
reduce rate of flow.

MAXIMUM LIFT
Gaso

line 10’ (3m)

Diesel 12’ (4.5 m

)

Additional specifications on page 15.

WARNING! Threaded pipe joints and connections should be sealed with the
appropriate sealant or sealant tape to minimize the possibility of leaks.

MAXIMUM LIFT
Gasoline 10’ (3m)
Diesel 18’ (5.5m)