D. mantel and wall projections – Heat & Glo Fireplace Heat & Glo Fireplace 6000C User Manual
Page 24
Heat & Glo • 6000C, 6000C-IPI, 8000C, 8000C-IPI • 2164-900 Rev. T • 9/12
24
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specified. Framing or finishing material closer than
the minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantels
Combustible Mantel Legs or Wall Projections
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
5
10
11
12
2-1/2
13
14
15
16
17
18
19
32
TO CEILING
9
10
11
12
8
7
6
5
4
3
25
18
A
B
INTERIOR WALL
TOP VIEW
MANTEL LEG OR WALL PROJECTIONS
FIREPLACE OPENING
Note: All measurements in inches.
If
A
minimum is ____, then
B
maximum is_____.
A
Inches
2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Millimeters
62
87
113
138
164
189
B
Inches
1
2
3
4
5
∞
Millimeters
25
51
76
102
127
∞
Note: Measurement is taken from top of the
opening, NOT the top of the fireplace.
Figure 5.4 Clearances to Mantel Legs or Wall Projections
(Acceptable on both sides of opening.)
Figure 5.3 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles