13

in 3 seconds and the icemaker automatically stops. The control board will signal this
problem using 7 beeps every 3 seconds.
The icemaker also automatically stops in cases of insufficient voltage (92Vac ± 5% or
less). The control board will signal this problem using 6 beeps every 3 seconds.
When the proper supply voltage is resumed, the icemaker automatically starts running
again.

f) LED Lights and Audible Alarm Safeties

The control board includes LED indicator lights, audible alarm safeties, and an output
test feature. The "POWER OK" LED indicates control voltage and will remain on unless
a control voltage problem occurs. The “POWER OK” LED flashes continuously when
the bin is full and DV energizes for a maximum of 5 minutes to drain the water tank.
At startup, a 5 second delay occurs to stabilize the circuit. LEDs 4 through 8 energize
and sequence from initial startup as listed in the table below. Note that the order of the
LEDs from the outer edge of the board is 5, 6, 8, 4, 7. For more information, see "2.
SEQUENCE OF OPERATION".

Sequence Step

LED

Energized

Components

Time LEDs are On

Min.

Max.

Avg.

1 Minute Fill Cycle

8

WV

60 seconds

Harvest Cycle

5, 6, 8

WV, HGV,
Comp

2 minutes

20 minutes 3 to 5 minutes

Last 0, 10, 30, or 50 seconds (adjustable by dip switch) of harvest, WV de-energizes
and PM energizes (LEDs 5, 6, and 7 are on)

Freeze Cycle

5, 7

Comp, PM,
FMS

5 minutes

freeze timer
setting

30 to 35 minutes

Drain

5, 6, 4

Comp, HGV,
DV

10 seconds 20 seconds

factory default
setting

The built in safeties shut down the unit and have alarms as listed below.

No. of Beeps

(every 3 sec.)

Type of Alarm

Notes

1

High Evaporator Temp.
(temperature > 127°F)
(53°C)

Check for harvest problem (stuck HGV or
relay), hot water entering unit, stuck HM, or
shorted thermistor.

2

Harvest Backup Timer
(harvest > 20 min. for two
cycles in a row)

C h e c k f o r o p e n t h e r m i s t o r, H G V n o t
opening, TXV leaking by, low charge,
inefficient Comp, or WRV leaking by.

3

Freeze Timer
(freeze > specified setting
for two cycles in a row)
Timer is factory set using
S1 dip switch 9 & 10

Check for a float switch stuck closed (up),
WV leaking by, HGV leaking by, PM not
pumping, TXV not feeding properly, low
charge, or inefficient Comp.

To reset the above safeties, press the "ALARM RESET" button with the power supply
on.