ProSoft Technology ICX30-HWC User Manual
Page 29
ICX30-HWC ♦ Industrial Cellular Gateway
Configuration Webpage
3G Cellular (M2M)
User Manual
ProSoft Technology, Inc.
Page 29 of 64
June 22, 2015
SNMP
Description
Read Community Name
Private: Read community string disabled
Public: Read community string enabled (default)
1st Trap Server IP
IP address of the 1st trap server. The ICX30-HWC will report the
trap message this IP address
2nd Trap Server IP
IP address of the 2nd trap server. The ICX30-HWC will report the
trap message this IP address
3rd Trap Server IP
IP address of the 3rd trap server. The ICX30-HWC will report the
trap message this IP address
SNMPv3
Use SNMP version 3 reporting and features
Serial Port
The RS-232 serial port supports the Modbus and DF1 industrial communication
protocols. For either protocol, a master or slave(s) can be connected to the
ICX30-HWC serial port.
Serial Port
Description
Baud Rate
Baud rate used on the ICX30-HWC serial port
Data
Data bits
Parity
Parity
Stop
Stop bits
Flow Control
Flow control enable or disable
Characters Timeout
Number of characters the ICX30-HWC will wait until a timeout is
determined from the device connected to the serial port.
Mode
Disable, Modbus Point-To-Point, Modbus Point-To-Multipoint, DF1
(see below)
Modbus Point-To-Point
Description
Server/Client
Server = ICX30-HWC serial port is connected to a Modbus slave
Client = ICX30-HWC serial port is connected to a Modbus master
Remote ICX30 Server IP
Address
(Client mode only) IP address of remote ICX30-HWC that is
connected to the Modbus slave.