ProSoft Technology 5202-DFNT-DFCM4 User Manual
Page 75
DFCM ♦ ProLinx Gateway
Reference
DF1 Master/Slave
Driver Manual
ProSoft Technology, Inc.
Page 75 of 88
October 15, 2010
[SECTION]/Item
Range
Description
Baud Rate:
This is the baud rate to be used on the port. Enter the baud
rate as a value. For example, to select 19K baud, enter
19200.
Ports 0, 1, 2 and 3
Baud Rate
Parameter Value
110
110
150
150
300
300
600
600
1200
12 or 1200
2400
24 or 2400
4800
48 or 4800
9600
96 or 9600
14,400
14, 114 or 14400
19,200
19, 192 or 19200
28,800
28, 288 or 28800
38,400
38, 384 or 38400
Ports 1, 2 and 3 only
Baud Rate
Parameter Value
57,600
57 or 576
115,200
115 or 1152
Parity:
None,
Odd, or
Even
This is the Parity code to be used for the port. The values
are as follows: None, Odd, Even.
Data Bits:
7 or 8
This parameter sets the number of data bits for each word
used by the protocol.
Stop Bits:
1 or 2
This parameter sets the number of stop bits to be used with
each data value sent.
RTS On:
0 to
65535
This parameter sets the number of milliseconds to delay
after RTS is asserted before the data will be transmitted.
RTS Off:
0 to
65535
This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem
signal will be set low.
Use CTS Line:
Yes or No This parameter specifies if the CTS modem control line is to
be used. If the parameter is set to No, the CTS line will not
be monitored. If the parameter is set to Yes, the CTS line will
be monitored and must be high before the module will send
data. Normally, this parameter is required when half-duplex
modems are used for communication (2-wire).
Request Timeout
1000
Request message timeout in milliseconds. Use default value.
Busy Timeout
550
Port Busy Timeout in milliseconds. Use default value.
ACK Timeout
0 to
65535
DLE-ACK timeout in milliseconds.
Retry Count:
0 to 10
This parameter specifies the number of times a command
will be retried if it fails.