Reference

DFCM ♦ ProLinx Gateway

Driver Manual

DF1 Master/Slave

Page 64 of 88

ProSoft Technology, Inc.

October 15, 2010

Function Code #509 - Protected Typed Logical Write (Two Address Fields)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled, 1=Continuous and 2=Conditional.

2

Virtual Database Address

This parameter defines the database address of the
first data point to be associated with the command.

3

Poll Interval

Minimum time in tenths of a second to wait before
polling with this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap
words, 2=Swap words & bytes and 3=swap bytes in
each word.

6

Node Address

Address of unit to reach on the data highway.

7

Function Code = 509

Logical Write Command

8

File Type

SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….

P1

9

File Number

SLC file number to be associated with the command.

P2

10

Element Number

The parameter defines the element in the file where
write operation will start.

P3

11

Not Used

This field is not used by the command. Values entered
in this column will be ignored.

P4

This function writes one or more words of data to a PLC data table.

Function Code #510 - Protected Typed Logical Write (Three Address Fields)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled, 1=Continuous and 2=Conditional.

2

Virtual Database Address

This parameter defines the database address of the first
data point to be associated with the command.

3

Poll Interval

Minimum time in tenths of a second to wait before
polling with this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.

6

Node Address

Address of unit to reach on the data highway.

7

Function Code = 510

Logical Write Command

8

File Type

SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….

P1

9

File Number

SLC file number to be associated with the command.

P2

10

Element Number

The parameter defines the element in the file where
write operation will start.

P3

11

Sub-Element Number

This parameter defines the sub-element for the
command. Refer to the AB documentation for a list of
valid sub-element codes.

P4