8.4.2 Command Function Codes
This section describes DFCM commands to be configured by the user.
Module Information Data
←
←
←
←
→
→
→
→
Device Information Data
1
2
3
4
5
6
7
8
9
10
11
Enable
Code
Internal
Address
Poll
Interval
Time
Count
Swap
Code
Node
Address
Function
Code
Function Parameters
Function Code #1 - Protected Write (Basic Command Set)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address of the first
data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before polling
with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 1
Protected Write Function
8
Word Address
Word address where to start the write operation.
P1
9 to 11
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function writes one or more words of data into a limited area of the slave
device. This function should work on the following devices: 1774-PLC, PLC-2,
PLC-3, PLC-5 and PLC-5/250.