8.1.3 DF1 Ports - Error/Status Data
The serial port (DF1 Master/Slave) Error and Status Data areas are discussed in
this section. The Error Status Pointer value is configured in the CFG file within
each of the individual [DF1 PORT X] sections.
The data area is initialized with zeros whenever the module is initialized. This
occurs during a cold-start (power-on), reset (reset push-button pressed) or a
warm-boot operation (commanded or loading of new configuration).
Example Internal
Database Address
Offset
Description
6300
0
Number of Command Requests
6301
1
Number of Command Responses
6302
2
Number of Command Errors
6303
3
Number of Requests
6304
4
Number of Responses
6305
5
Number of Errors Sent
6306
6
Number of Errors Received
6307
7
Configuration Error Word
6308
8
Current Error Code
6309
9
Last Error Code
Refer to the following Error Codes section to interpret the status/error codes
present in the data area.
8.1.4 Master Port: Command Errors
The individual command errors for each master port are returned to the address
locations specified in the following table.
DF1 Port
Address Range
0
6310 to 6409
1
6710 to 6809
2
7110 to 7209
3
7510 to 7609
The first word in the register location defined contains the status/error code for
the first command in the port’s command list. Each successive word in the
command error list is associated with the next command in the list.