beautypg.com

ProSoft Technology 5202-DFNT-DFCM4 User Manual

Page 42

background image

Commands Supported by the Module

DFCM ♦ ProLinx Gateway

Driver Manual

DF1 Master/Slave

Page 42 of 88

ProSoft Technology, Inc.

October 15, 2010

In order to retrieve data from the modules database register 200, the remote

master would issue a command using the address N8:0. In order to interface with

database base register 405, the remote master would use the address N9:5. The

following table outlines the complete file emulation for the module:

Register Range

File Start

File End

Content

Size

0 to 4999

N7:0

N31:199

User Data

5000

5000 to 5009

N32:0

N32:9

Backplane Configuration

10

5010 to 5039

N32:10

N32:39

Port 1 Setup

30

5040 to 5069

N32:40

N32:69

Port 2 Setup

30

5070 to 5199

N32:70

N32:199

Reserved

130

5200 to 6399

N33:0

N38:199

Port 1 Commands

1200

6400 to 7599

N39:0

N44:199

Port 2 Commands

1200

7600 to 7700

N45:0

N45:199

Misc. Status Data

200

7800 to 7999

N46:0

N46:199

Command Control

200

8000 to 9999

N47:0

N56:199

Reserved

2000


All the data in the module is available to a remote host. This permits the host

device to remotely configure the module and view the status data.

7.1.1 Command Entry Formats

Note: The format of each command in the list depends on the function being executed. Refer to
the Reference chapter for a complete discussion of the DF1 commands supported by the module
and of the structure and content of each command.

The following table shows the structure of the configuration data necessary for

each of the supported commands.