ProSoft Technology 5202-DFNT-DFCM4 User Manual
Page 42

Commands Supported by the Module
DFCM ♦ ProLinx Gateway
Driver Manual
DF1 Master/Slave
Page 42 of 88
ProSoft Technology, Inc.
October 15, 2010
In order to retrieve data from the modules database register 200, the remote
master would issue a command using the address N8:0. In order to interface with
database base register 405, the remote master would use the address N9:5. The
following table outlines the complete file emulation for the module:
Register Range
File Start
File End
Content
Size
0 to 4999
N7:0
N31:199
User Data
5000
5000 to 5009
N32:0
N32:9
Backplane Configuration
10
5010 to 5039
N32:10
N32:39
Port 1 Setup
30
5040 to 5069
N32:40
N32:69
Port 2 Setup
30
5070 to 5199
N32:70
N32:199
Reserved
130
5200 to 6399
N33:0
N38:199
Port 1 Commands
1200
6400 to 7599
N39:0
N44:199
Port 2 Commands
1200
7600 to 7700
N45:0
N45:199
Misc. Status Data
200
7800 to 7999
N46:0
N46:199
Command Control
200
8000 to 9999
N47:0
N56:199
Reserved
2000
All the data in the module is available to a remote host. This permits the host
device to remotely configure the module and view the status data.
7.1.1 Command Entry Formats
Note: The format of each command in the list depends on the function being executed. Refer to
the Reference chapter for a complete discussion of the DF1 commands supported by the module
and of the structure and content of each command.
The following table shows the structure of the configuration data necessary for
each of the supported commands.