beautypg.com

ProSoft Technology 5202-DFNT-DFCM4 User Manual

Page 54

background image

Reference

DFCM ♦ ProLinx Gateway

Driver Manual

DF1 Master/Slave

Page 54 of 88

ProSoft Technology, Inc.

October 15, 2010

8.4

DF1 Command Set For ProSoft Technology Communication Modules

8.4.1 Introduction

This document contains a complete description of the command set required to

communicate with DF1 protocol devices using a ProSoft communication module.

ProSoft communication modules that contain a virtual DF1 master device use

this command set to control and monitor data in DF1 protocol devices. These

include PLC, SLC, MicroLogix and ControlLogix controllers and field devices

supporting the DF1 protocol. ProSoft supports the DF1 protocol on both the serial

and network interface. The network interface requires the use of the port service

address 0xAF12 as specified in the ControlNet Specification. supports this

feature in the ControlLogix, PLC5 xx/E and SLC 5/05 processors.
The ProSoft modules contain a virtual database that is defined by the user. This

database is used as the source for write commands and the destination for read

commands issued on the virtual DF1 master devices. The module interfaces data

contained in remote DF1 slave devices to the virtual database using the DF1

master. User commands are issued out of the DF1 master from a command list.

These commands gather or control data in the DF1 slave devices. The following

illustration shows the relationships discussed above:

Each command issued from the DF1 master contains a field that indicates the

location in the virtual database to be associated with the command. Care must

be taken when designing a system to be sure the read and write data regions for

the database do not overlap for a single device. The read area of one device can

overlap the write section of another device to transfer the data from one slave

device to another.