8.7.1 Parameter Descriptions
[SECTION]/Item
Range
Description
[DF1 Master Port]
Configuration Header for DF1 Master Port
Local Station ID:
0 to 255
This parameter specifies the local station ID for all DF1
messages sent from this master port. A value of 255 will
cause the slave address to be ignored and the address
issued in the master request packet to be used as the slave
ID.
Termination Type:
BCC or
CRC
This parameter specifies the error checking for all DF1
messages. BCC or CRC
Baud Rate:
This is the baud rate to be used on the port. Enter the baud
rate as a value. For example, to select 19K baud, enter
19200.
Ports 0, 1, 2 and 3
Baud Rate
Parameter Value
110
110
150
150
300
300
600
600
1200
12 or 1200
2400
24 or 2400
4800
48 or 4800
9600
96 or 9600
14,400
14, 114 or 14400
19,200
19, 192 or 19200
28,800
28, 288 or 28800
38,400
38, 384 or 38400
Ports 1, 2 and 3 only
Baud Rate
Parameter Value
57,600
57 or 576
115,200
115 or 1152
Parity:
None,
Odd, or
Even
This is the Parity code to be used for the port. The values
are as follows: None, Odd, Even.
Data Bits:
7 or 8
This parameter sets the number of data bits for each word
used by the protocol.
Stop Bits:
1 or 2
This parameter sets the number of stop bits to be used with
each data value sent.
RTS On:
0 to
65535
This parameter sets the number of milliseconds to delay
after RTS is asserted before the data will be transmitted.
RTS Off:
0 to
65535
This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem
signal will be set low.