ProSoft Technology 5228-DFNT-HART User Manual
Page 89
ProLinx-HART ♦ ProLinx Gateway
Reference
HART Master with Analog I/O
Driver Manual
ProSoft Technology, Inc.
Page 89 of 104
October 13, 2011
Bit 7 of First Byte = 0
Command Error
Bit 2
Analog Output Saturated
Bit 1
Variable (not Primary) Out Of Limits
Bit 0
Primary Variable Out of Limits
Command Specific Errors
8
Update Failed
Update In Progress
Set to Nearest Possible Value
9
Applied Process Too High
Lower Range Value Too High
Not in Fixed Current Mode
10
Applied Process Too Low
Lower Range Value Too Low
Multi-drop Not Supported
11
In Multi-drop Mode
Invalid Transmitter Variable Code
Upper Range Value Too High
12
Invalid Unit Code
Upper Range Value Too Low
13
Both Range Values Out of Limits
14
Pushed Upper Range Value Over Limit
Span Too Small
HART Configuration Error Word
Bit
Code
Description
0
0x0001
Enabled not set to Y or N
1
0x0002
Enable Handheld not set to Y or N
2
0x0004
Primary Master not set to Y or N
3
0x0008
Invalid Preambles (1 to 50)
4
0x0010
Invalid Short Address Retries (0 to 50)
5
0x0020
Invalid Long Address Retries (0 to 50)
6
0x0040
Invalid Retries After Error (0 to 50)
7
0x0080
Invalid Poll Time After Error (0 to 10000)
8
0x0100
Invalid DB Address Status
9
0x0200
Invalid Command Count
10
0x0400
Memory Error in allocating commands
11
0x0800
Memory Error in allocating command fixed data
12
0x1000
Memory Error in allocating TX/RX buffers
13
0x2000
HART Board not found
14
0x4000
Cannot initialize HART channel
15
0x8000
reserved