ProSoft Technology 5228-DFNT-HART User Manual

Page 29

background image

ProLinx-HART ♦ ProLinx Gateway

HART Protocol Configuration

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 29 of 104

October 13, 2011

3.2

[HART PORT x]

The configuration file sections [HART PORT 0] through [HART PORT 3] (for 4 channel

modules) or [HART PORT 0] through [HART PORT 7] (for 8 channel modules) set HART

channel communication parameters, define the protocol specific parameters, and set the

command list parameters. The parameters are the same for all channels. The command

list parameters for each HART channel are entered in a different section in the

configuration file.

3.2.1 Enabled

Y or N
This parameter enables or disables the specific HART channel. If the parameter is set to

"Y", the channel will be utilized. If set to "N", the channel will not be used.

3.2.2 Preambles

2 to 50
This parameter defines the number of 0xFF characters (preambles) that will be placed at

the start of each HART frames.

3.2.3 Primary Master

Yes or No
This parameter specifies the Link Quiet / Slave Timeout. If set to Yes, the selected Link

Quiet / Slave Timeout is 305 milliseconds which corresponds to the Primary Master. If set

to No, then this time is 380 milliseconds which corresponds to the Secondary Master.

3.2.4 Retry Count

0 to 10
This parameter sets the number of retries for a command if the command response is not

received from the slave device. This parameter is normally set to a value of 3. The

module will accept values of 0 to 10.

3.2.5 DB Address Status

-1, 0 to 3999
This parameter is utilized to set the database address in the module where the status

word for the channel will be placed. If the parameter is set to -1, the word value will not

be placed in the database. If a value from 0 to 3999 is set for the parameter, the status

word for the channel will be placed at the specified database offset. This word is bit

mapped with each bit representing a slave device. The bit will be set if slave device has a

communication error.