beautypg.com

ProSoft Technology 5228-DFNT-HART User Manual

Page 49

background image

ProLinx-HART ♦ ProLinx Gateway

Reference

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 49 of 104

October 13, 2011

COMMAND 14 - Read PV Sensor Info

Description

This command gets information about the Primary Variable sensor, like limits and span.

Write Parameters

NONE

Floating Point Data Returned

Word

High Byte

Low Byte

0

Upper Sensor Limit

1
2

Lower Sensor Limit

3
4

Minimum Span

5

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

Sensor Serial Number 0

Sensor Serial Number 1

2

Sensor Serial Number 2

Unit Codes for Sensor Limits and Span

This manual is related to the following products: