4.2
HART Common Practice Commands
COMMAND 33 - Read Transmitter Variables
Description
This command gets four user selected dynamic Variables.
Write Parameters
Word
High Byte
Low Byte
0
Transmitter Variable Code For Slot 0
Transmitter Variable Code For Slot 1
1
Transmitter Variable Code For Slot 2
Transmitter Variable Code For Slot 3
Floating Point Data Returned
Word
High Byte
Low Byte
0
Variable for Slot 0
1
2
Variable for Slot 0
3
4
Variable for Slot 2
5
6
Variable for Slot 3
7
Integer Data Returned
Word
High Byte
Low Byte
0
STATUS WORD
1
Transmitter Variable Code For Slot 0
Units Code for Slot 0 Variable
2
Transmitter Variable Code For Slot 1
Units Code for Slot 1 Variable
3
Transmitter Variable Code For Slot 2
Units Code for Slot 2 Variable
4
Transmitter Variable Code For Slot 3
Units Code for Slot 3 Variable