ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 24 of 104

ProSoft Technology, Inc.

October 13, 2011

The following topics describe the modes of module operation.

Auto-Poll Disabled Mode

If the auto-polling feature is disabled (Auto-Poll Code = N), the module functions as

shown in the following diagram:

Only the user commands are executed and all data is placed in and sourced from the

module's internal database. The user is responsible for constructing all commands to

control and monitor the instruments attached to the channel.

Point-to-Point Mode

Important: If the HART device address is 0 you must configure the channel for

Point-to-Point mode.

In point-to-point mode, the module only polls for a single instrument with a polling

address of zero. When the instrument is found by the channel, it continuously polls for the

data using command 3. Occasionally, it will poll for the configuration information for the

device. This is accomplished with HART commands 13, 14 and 15. Less frequently, the

channel will perform a HART command 0 request to see if any of the data for the

instrument has changed. If communications is lost with the device, the module will try to

establish communications with the device using command 0. If user commands are

present and enabled, they will be executed after each data poll.