beautypg.com

ProSoft Technology 5228-DFNT-HART User Manual

Page 67

background image

ProLinx-HART ♦ ProLinx Gateway

Reference

HART Master with Analog I/O

Driver Manual

ProSoft Technology, Inc.

Page 67 of 104

October 13, 2011

COMMAND 45 - Trim DAC Zero

Description

This command calibrates the device Digital to analog converter zero. This is done by

writing the same current value that is measured in the loop.

Write Parameters

Word

High Byte

Low Byte

0

Floating Point measured current (mA)

1

Floating Point Data Returned

Word

High Byte

Low Byte

0

Floating Point Current (mA)

1

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

This manual is related to the following products: