COMMAND 49 - Write PV Sensor Serial Number
Description
This command changes the sensor serial number of the Primary Variable.
Write Parameters
Word
High Byte
Low Byte
0
Sensor Serial Number (Byte 0)
Sensor Serial Number (Byte 1)
1
Sensor Serial Number (Byte 2)
Sensor Serial Number (Byte 2)
Floating Point Data Returned
NONE
Integer Data Returned
Word
High Byte
Low Byte
0
STATUS WORD
1
Sensor Serial Number (Byte 0)
Sensor Serial Number (Byte 1)
2
Sensor Serial Number (Byte 2)
0