HART Protocol Configuration

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 38 of 104

ProSoft Technology, Inc.

October 13, 2011

3.4.1 Internal Database Re-mapping

Depending on the application, you may need to copy data from one section of the

module’s internal database to another section. The [Data Map] section of the CFG file
allows a user to selectively copy data registers, one register up to 100 registers at a time,

from one internal database to another. Up to 200 entries can be made in the [Data Map]
section, providing a wide and powerful range of functionality.

3.4.2 From Address

0 to 3999
This field specifies the internal database register to copy from. This address can range

from the Data area as well as the Status Data Area of the product

3.4.3 To Address

0 to 3999
The destination for the copy is always going to be the Register Data area.

3.4.4 Register Count

1 to 100
This parameter specifies the number of registers to copy.

3.4.5 Swap Code

0, 1, 2, 3
There may be a need to swap the order of the bytes in the registers during the copy

process in order to change from alignment of bytes between dissimilar protocols. This

parameter is helpful when dealing with floating-point or other multi-register values, as

there is no standard method of storage of these data types in slave devices.
The following table defines the values and their associated operations:

Swap Code

Description

0

None - No Change is made in the byte ordering (1234 = 1234)

1

Words - The words are swapped (1234=3412)

2

Words & Bytes - The words are swapped then the bytes in each word are

swapped (1234=4321)

3

Bytes - The bytes in each word are swapped (1234=2143)