Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 48 of 104

ProSoft Technology, Inc.

October 13, 2011

COMMAND 13 - Read Tag, Descriptor and Date

Description

This command reads an ASCII Tag which identifies the device, an ASCII descriptor of the

device and the last Date it has been configured.

Write Parameters

NONE

Floating Point Data Returned

NONE

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

TAG ASCII Character 0

TAG ASCII Character 1

2

TAG ASCII Character 2

TAG ASCII Character 3

3

TAG ASCII Character 4

TAG ASCII Character 5

4

TAG ASCII Character 6

TAG ASCII Character 7

5

Descriptor ASCII Character 0

Message ASCII Character 1

.
.
.

.
.
.

12

Descriptor ASCII Character 14

Message ASCII Character 15

13

Date

Date

14

Date

0