Protocol Error Codes

These are error codes that are part of the HART protocol. The standard HART error

codes are shown in the following tables:

Error Code Word

First Byte

Second Byte

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Bit 7 of First Byte = 1
COMMUNICATION ERROR

First Byte
Bit 6

Parity Error

Bit 5

Overrun Error

Bit 4

Framing Error

Bit 3

Checksum Error

Bit 2

Reserved

Bit 1

Rx Buffer Overflow

Bit 0

Undefined

Second Byte
Bit 0 To Bit 7

All 0

Bit 7 of First Byte = 0
Command Error

First Byte
Bits 6 To 0 (not Bit-mapped):
0

No Error

1

Undefined

2

Invalid Selection

3

Passed Parameter Too Large

4

Passed Parameter Too Small

5

Too Few Data Bytes Received

6

Transmitter-specific Command Error

7

In Write-protect Mode

8 to 15

Command Specific Errors (see Below)

16

Access Restricted

32

Device Is Busy

64

Command Not Implemented

Second Byte
Bit 7

Device Malfunction

Bit 6

Configuration Changed

Bit 5

Cold Start

Bit 4

Unused

Bit 3

Output Current Fixed

This manual is related to the following products: