beautypg.com

Command 58 - write unit tag descriptor date – ProSoft Technology 5228-DFNT-HART User Manual

Page 80

background image

Reference

ProLinx-HART ♦ ProLinx Gateway

Driver Manual

HART Master with Analog I/O

Page 80 of 104

ProSoft Technology, Inc.

October 13, 2011

COMMAND 58 - Write Unit Tag Descriptor Date

Description

This command writes an ASCII Tag which identifies the device, an ASCII descriptor of

the device and the last Date it has been configured.

Write Parameters:

Word

High Byte

Low Byte

0

Packed ASCII TAG Byte 0

Packed ASCII TAG Byte 1

1

Packed ASCII TAG Byte 2

Packed ASCII TAG Byte 3

2

Packed ASCII TAG Byte 4

Packed ASCII TAG Byte 5

3

Packed ASCII Descriptor Byte 0

Packed ASCII Descriptor Byte 1

.
.
.

.
.
.

8

Packed ASCII Descriptor Byte 10

Packed ASCII Descriptor Byte 11

9

Date

Date

10

Date

0

Floating Point Data Returned

NONE

Integer Data Returned

Word

High Byte

Low Byte

0

STATUS WORD

1

TAG ASCII Character 0

TAG ASCII Character 1

2

TAG ASCII Character 2

TAG ASCII Character 3

3

TAG ASCII Character 4

TAG ASCII Character 5

4

TAG ASCII Character 6

TAG ASCII Character 7

5

Descriptor ASCII Character 0

Message ASCII Character 1

.
.
.

.
.
.

12

Descriptor ASCII Character 14

Message ASCII Character 15

13

Date

Date

14

Date

0

This manual is related to the following products: