Emerson OpenComms-485 User Manual

Page 38

background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

35

Free cooling run
hours

30146

-

1

Hour

S505

Electrical Heaters
#1 run hours

30147

-

1

Hour

S507

Electrical Heaters
#2 run hours

30148

-

1

Hour

S508

Electrical Heaters
#3 run hours

30149

-

1

Hour

S509

Hot Water / Hot
Gas run hours

30150

-

1

Hour

S506

Daily High
Temperature

30151

-

x10

S313

Daily High Temp
Time

30152

-

x1

Hh:mm

S313

Daily Low
Temperature

30153

-

x10

S314

Daily Low Temp
Time

30154

-

x1

Hh:mm

S314

Daily High
Humidity

30155

-

x1

%RH

S315

Daily High Hum
Time

30156

-

x1

Hh:mm

S315

Daily Low
Humidity

30157

-

x1

%RH

S316

Daily Low Hum
Time

30158

-

x1

Hh:mm

S316

[1] Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
[2] Timer mode: 0 = no, 1= yes.
[3] Type of DT Room-Glycol: 0 = no, 1=contact, 2=value.
[4] Predictive Hum Control: 0=relative, 1=compensated, 2=predictive.
[5] Temp Control Algorithm: 0=proportional, 1=PD, 2=PDI; 3=intelligent;
[6] When VFD is set to manual mode(coil 22), the host can control the VFD by the value of register 40019. The Manual
VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to
periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.

[7] Operating State

:

Bit 0-1: 00 unit off, 01 unit on, 10 unit standby

Bit 2-3: 00 auto, 01 manual
Bit 4-7: 0000 none,

0001 local user,
0010 alarm,
0011 schedule,
0100 remote user,
0101 external device,
0110 local display

[8] Alarm state bit map:

Bit0 =. Reset state

bit1 = Active state ;
bit2 = Acknowledge state,
bit3-7 = Alarm Type,:

00000: Message

00001:

Warning

00010:

Alarm

[9] Free-cool state: 0= Off, 1= Start, 2= On.