Liebert powersure interactive 2, Supported modbus points – Emerson OpenComms-485 User Manual
Page 18
REV. 5
7/6/2007
Liebert Monitoring Group –Development
15
Liebert PowerSure Interactive 2
Supported Modbus Points
Data Point
Status
Coil
# of Reg. Scale Notes / Units
Audible Alarm Enabled
10002
2
1
1
Automatic Battery Test
Enabled 10003
3
1
1
DC-To-DC Converter
On
10042
1
1
Battery Charger On
10044
1
1
Load Circuit 1 State
10057
1
1
Load Circuit 2 State
10058
1
1
Load Circuit 3 State
10059
1
1
Load Circuit 4 State
10060
1
1
Load Circuit 5 State
10061
1
1
Load Circuit 6 State
10062
1
1
Load Circuit 7 State
10063
1
1
Load Circuit 9 State
10065
1
1
Load Circuit 10 State
10066
1
1
Load Circuit 11 State
10067
1
1
Load Circuit 12 State
10068
1
1
Load Circuit 13 State
10069
1
1
Load Circuit 14 State
10070
1
1
Load Circuit 15 State
10071
1
1
Load Circuit 16 State
10072
1
1
Load On Inverter
10073
1
1
Boost Mode On
10075
1
1
Buck Mode On
10076
1
1
Replace Battery
10081
1
1
Battery Under Test
10082
1
1
Shutdown Reason -
Over Temperature
10086
1
1
Shutdown Reason -
Overload
10087
1
1
Shutdown Reason -
Output Short
10089
1
1
Shutdown Reason -
Line Neutral Swap
10090
1
1
Shutdown Reason -
Low Battery
10092
1
1
Shutdown Reason -
Remote Shutdown
10093
1
1
Shutdown Reason -
Input Under Voltage
10094
1
1
Shutdown Reason -
10096
1
1