Liebert Monitoring Group –Development

34

Events/Alarm

EventCount

Summary Alarm
Status [8]

30102

-

-

-

EnvState.

AlarmState

Fan Ramp

30103

-

1

%

EnvState.

FanRamp

Cooling Ramp

30104

-

1

%

EnvState.

CoolRamp

Free Cooling
Ramp

30105

-

1

%

EnvState.

FCRamp

Heating Ramp

30106

-

1

%

EnvState.

HeatRamp

Humidification
Ramp

30107

-

1

%

EnvState.

HumRamp

Dehumidifier
Ramp

30108

-

1

%

EnvState.

DehumRamp

FreeCooling
Status [9]

30109

-

1

%

U312

Return
Temperature

30110

-

x10

EnvState.
ActTemp

Actual
Temperature SP

30111

-

x10

U301

(ActTemp

Set)

Supply
Temperature

30112

-

x10

EnvState.ActSup

Actual Supply
Temperature SP

30113

-

x10

EnvState.

ActSupSet

FC Temperature

30115

-

x10

U309

Sensor A
Temperature

30116

-

x10

U303

Sensor B
Temperature

30117

-

x10

U305

Sensor C
Temperature

30118

-

x10

U307

Digi Scroll 1
Temperature

30119

-

x10

U310

Digi Scroll 2
Temperature

30120

-

x10

U311

Return Humidity

30130

-

1

%

EnvState.ActTe
mp

Actual Humidity
SP

30131

-

1

%

U302

(ActHumS

et)

Sensor A
Humidity

30132

-

1

%

U304

Sensor B
Humidity

30133

-

1

%

U306

Sensor C
Humidity

30134

-

1

%

U308

Fan Run Hour

30141

-

1

Hour

S502

Compressor 1
Run Hour

30142

-

1

Hour

S503

Compressor 2
Run Hour

30143

-

1

Hour

S504

Humidifier run
hours

30144

-

1

Hour

S510

Dehumidification
run hours

30145

-

1

Hour

S511