Emerson OpenComms-485 User Manual
Page 31
REV. 5
7/6/2007
Liebert Monitoring Group –Development
28
Input Voltage L1
30153
1
1
V
Input Current
30154
1
1
A
Bypass Voltage L1
30159
1
1
V
Bypass Current L1
30160
1
1
A
Output Voltage L1
30163
1
1
V
Output Current L1
30164
1
1
A
Input Voltage L2
30203
1
1
V
Input Current L2
30204
1
1
A
Bypass Voltage L2
30209
1
1
V
Bypass Current L2
30210
1
1
A
Output Voltage L2
30213
1
1
V
Output Current L2
30214
1
1
A
Input Voltage L3
30253
1
1
V
Input Current L3
30254
1
1
A
Bypass Voltage L3
30259
1
1
V
Bypass Current L3
30260
1
1
A
Output Voltage L3
30263
1
1
V
Output Current L3
30264
1
1
A
Black Out Count
30301
1
1
Brown Out Count
30302
1
1
Transient Count
30301
1
1
Silent Audible Alarm
40101
any value
Battery Start
40102
1
1
1=Start, 0=Abort
Open UPS Output
Switch
40104
Delay time in Second, last digit
will be ignored
Reboot UPS Output
Switch
40105
1
1
Delay time in Second, last digit
will be ignored
Close UPS Output
Switch
40106
Delay time in Second, last digit
will be ignored
Transfer Load to
Bypass
40107
1
1
any value
Transfer Load to
Inverter
40108
any
value
Reset UPS Statistic
data
40111
1
1
any value
Turn UPS Outlets On
40112
1
1
Bitmap mask for Outlet 1-16. all
bits set to 1 will be turn On
Turn UPS Outlets Off
40113
1
1
Bitmap mask for Outlet 1-16. all
bits set to 1 will be turn Off