Battery Charger Fail

10234

1

1

Data Point

Input

Register

Holding

Register

# of

Reg.

Scale

Notes / Units

Number Of Input Lines

30004

40004

1

1

Bits 12 - 15

Number Of Bypass
Lines

30004

40004

1

1

Bits 4 - 7

Number Of Output
Lines

30004

40004

1

1

Bits 8 - 11

Number Of
SubModules

30009

40009

1

1

Load Circuit Present

30013

40013

1

There are 16 possible Load
Circuits. So each bit represents 1
load circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so
on. If the bit is 1 then the Load
Circuit is supported.

Nominal Power Rating

30021

40021

2

1

VA

Nominal Input Voltage

30027

40027

1

1

V

Nominal Output
Voltage

30028

40028

1

1

V

Nominal Static Bypass
Switch Voltage

30029 40029 1

1 V

Nominal Input Current

30030

40030

1

1

A

Nominal Input
Frequency

30031 40031 1

10

Hz

Nominal Output
Frequency

30032

40032

1

10

Hz

Nominal Power Factor

30033

40033

1

100

Nominal Battery
Voltage

30034

40034

1

1

V

Device Low Battery
Time

30053 40053 1

1 min

Load (Apparent
Power)

30102

2

1

VA

Load (Real Power)

30104

2

1

W

Load / Capacity

30106

1

1

%

Input Frequency

30107

1

10

Hz

Output Frequency

30108

1

10

Hz

Bypass Frequency

30109

1

10

Hz

Battery Charge Status

30112

1

1

1 - 100% Charged
2 - Less than 100% Charged

Battery Voltage

30113

1

1

V

Battery Current

30114

1

1

A

Battery Time
Remaining

30115

1 1

min

Battery Charge
Percentage

30116

1

1

%

Battery Test Result

30130

1

1

1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited