Emerson OpenComms-485 User Manual
Page 30
REV. 5
7/6/2007
Liebert Monitoring Group –Development
27
Battery Charger Fail
10234
1
1
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number Of Input Lines
30004
40004
1
1
Bits 12 - 15
Number Of Bypass
Lines
30004
40004
1
1
Bits 4 - 7
Number Of Output
Lines
30004
40004
1
1
Bits 8 - 11
Number Of
SubModules
30009
40009
1
1
Load Circuit Present
30013
40013
1
There are 16 possible Load
Circuits. So each bit represents 1
load circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so
on. If the bit is 1 then the Load
Circuit is supported.
Nominal Power Rating
30021
40021
2
1
VA
Nominal Input Voltage
30027
40027
1
1
V
Nominal Output
Voltage
30028
40028
1
1
V
Nominal Static Bypass
Switch Voltage
30029 40029 1
1 V
Nominal Input Current
30030
40030
1
1
A
Nominal Input
Frequency
30031 40031 1
10
Hz
Nominal Output
Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
Nominal Battery
Voltage
30034
40034
1
1
V
Device Low Battery
Time
30053 40053 1
1 min
Load (Apparent
Power)
30102
2
1
VA
Load (Real Power)
30104
2
1
W
Load / Capacity
30106
1
1
%
Input Frequency
30107
1
10
Hz
Output Frequency
30108
1
10
Hz
Bypass Frequency
30109
1
10
Hz
Battery Charge Status
30112
1
1
1 - 100% Charged
2 - Less than 100% Charged
Battery Voltage
30113
1
1
V
Battery Current
30114
1
1
A
Battery Time
Remaining
30115
1 1
min
Battery Charge
Percentage
30116
1
1
%
Battery Test Result
30130
1
1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited