beautypg.com

Emerson OpenComms-485 User Manual

Page 36

background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

33

Hour:Minute

Sleep Interval 2
Start Time
Hour:Minute

30042

40042

1

MSB:Hr

U607

(FROM)

Sleep Interval 2
End Time
Hour:Minute

30043

40043

1

MSB:Hr

U607

(TO)

Timer Dead Band

30044

40044

1

X10

U611

Manual VSD
Timer/Counter[6]

30045 40045

1

High
Temperature

30050

40050

1

X10

U203

Low Temperature

30051

40051

1

X10

U204

High
Temperature
Sensor A

30052

40052

1

X10

U208

Low Temperature
Sensor A

30053

40053

1

X10

U209

High Humidity

30054

40054

1

1

%

U205

Low Humidity

30055

40055

1

1

%

U206

High Humidity
Sensor A

30056

40056

1

1

%

U210

Low Humidity
Sensor A

30057

40057

1

1

%

U211

Fan Run Hour
Threshold

30070

40070

1

Hour

U502

Compressor 1
Run Hour
Threshold

30071

40071

1

Hour

U503

Compressor 2
Run Hour
Threshold

30072

40072

1

Hour

U504

Humidifier run
hours Threshold

30073

40073

1

Hour

U510

Dehumidification
run hours
Threshold

30074

40074

1

Hour

U511

CW/FC run hours
Threshold

30075

40075

1

Hour

U505

Electrical Heaters
#1 run hours
Threshold

30076

40076

1

Hour

U507

Electrical Heaters
#2 run hours
Threshold

30077

40077

1

Hour

U508

Electrical Heaters
#3 run hours
Threshold

30078

40078

1

Hour

U509

Hot Water / Hot
Gas run hours
Threshold

30079

40079

1

Hour

U506

Operating State
[7]

30100

-

1

-

EnvState.
OperatingState

Number of Active

30101

-

-

-

EnvState.