Liebert Monitoring Group –Development

30

Humidification On

10030

-

1

HumSym

Dehumidification On

10031

-

1

DehumSym

Audible Alarm On

10032

-

1

HornSym

Reserved

10033

-

1

087

MAIN FAN OVERLOAD

10034

-

1

006

LOSS OF AIRFLOW

10035

-

1

007

LOSS OF FLOW

10036

-

1

107

COMP 1 HIGH PRESSURE

10037

-

1

001

COMP 1 LOW PRESSURE

10038

-

1

002

COMP 1 OVERLOAD

10039

-

1

071

COMP 1 PUMPDOWN FAIL

10040

-

1

091

COMP 2 HIGH PRESSURE

10041

-

1

058

COMP 2 LOW PRESSURE

10042

-

1

059

COMP 2 OVERLOAD

10043

-

1

072

COMP 2 PUMPDOWN FAIL

10044

-

1

096

DIG SCROLL1 HIGH TEMP

10045

-

1

097

DIG SCROLL2 HIGH TEMP

10046

-

1

098

SMOKE DETECTED

10047

-

1

104

WATER UNDER FLOOR

10048

-

1

105

HUMIDIFIER PROBLEM

10049

-

1

086

STBY GLYCOL PUMP ON

10050

-

1

108

STANDBY UNIT ON

10051

-

1

109

COND PUMP-HIGH WATER

10052

-

1

106

ROOM SENSOR FAILURE

10053

-

1

031

LOSS COMPRESSOR
POWER

10054

-

1

135

LOSS OF AIR BLOWER 1

10055

-

1

017

HUMIDIFIER LOW WATER

10058

-

1

153

HUMIDIFIER HIGH AMPS

10059

-

1

152

HIGH TEMPERATURE

10060

-

1

016

LOSS OF POWER

10061

-

1

142

UNSPECIFIED EVENT(S) [1]

10064

-

1

HIGH CW TEMP

10065

-

1

003

RESERVED 10066

-

1

005

HIGH ROOM TEMP

10067

-

1

018

LOW ROOM TEMP

10068

-

1

019

HIGH ROOM HUM

10069

-

1

020

LOW ROOM HUM

10070

-

1

021

HIGH TEMP SENSOR A

10071

-

1

022

LOW TEMP SENSOR A

10072

-

1

023

HIGH HUM SENSOR A

10073

-

1

024

LOW HUM SENSOR A

10074

-

1

025

LOSS OF CW FLOW

10075

-

1

004

CLOGGED FILTERS

10076

-

1

008

SUPPLY SENSOR FAILURE

10077

-

1

029

FREECOOL TEMP SENSOR

10078

-

1

062