Liebert nx, Supported modbus points – Emerson OpenComms-485 User Manual
Page 10
REV. 5
7/6/2007
Liebert Monitoring Group –Development
7
Liebert Nx
Supported Modbus Points
Data Point
Status
Coil
# of Reg. Scale Notes / Units
Economode
10005
5
DC-To-DC Converter
On
10042
Battery Charge
Compensation
10046
Inverter Ready
10047
Power Factor
Correction State
10050
Battery Charge Mode
10051
Load On Inverter
10073
Bypass Active
10074
Battery Under Test
10082
Load On Battery
10128
Overload Transfer To
Bypass
10131
Input Switch Open
10137
Generator
Disconnected
10141
Bypass Transfer
Count Block
10147
Static Bypass Switch
Disabled
10148
Low Battery -
Shutdown Imminent
10152
Output Overload
10154
UPS Load Joint
Mode
10156
Output Off
10158
Inverter
Unsynchronized
10160
Main Neutral Lost
10161
Fan Failure
10169
Ambient Over
Temperature
10173
Rectifier Over
Temperature
10174
Rectifier Inductor
Over Temperature
10175
Inverter Over
Temperature
10176
Inverter Inductor
Over Temperature
10177
Battery Converter
10179