Liebert nx, Supported modbus points – Emerson OpenComms-485 User Manual

Page 10

background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

7

Liebert Nx

Supported Modbus Points

Data Point

Status

Coil

# of Reg. Scale Notes / Units

Economode

10005

5

DC-To-DC Converter
On

10042

Battery Charge
Compensation

10046

Inverter Ready

10047

Power Factor
Correction State

10050

Battery Charge Mode

10051

Load On Inverter

10073

Bypass Active

10074

Battery Under Test

10082

Load On Battery

10128

Overload Transfer To
Bypass

10131

Input Switch Open

10137

Generator
Disconnected

10141

Bypass Transfer
Count Block

10147

Static Bypass Switch
Disabled

10148

Low Battery -
Shutdown Imminent

10152

Output Overload

10154

UPS Load Joint
Mode

10156

Output Off

10158

Inverter
Unsynchronized

10160

Main Neutral Lost

10161

Fan Failure

10169

Ambient Over
Temperature

10173

Rectifier Over
Temperature

10174

Rectifier Inductor
Over Temperature

10175

Inverter Over
Temperature

10176

Inverter Inductor
Over Temperature

10177

Battery Converter

10179