Liebert ups series 300, Supported modbus points – Emerson OpenComms-485 User Manual

Page 29

background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

26

Liebert UPS Series 300

Supported Modbus Points

Data Point

Status

Coil

# of

Reg.

Scale

Notes / Units

Automatic Restart
Enabled

10001

1

1

1

Battery Charge
Compensation

10046

1

1

Inverter Ready

10047

1

1

Load Circuit 1 State

10057

1

1

Load Circuit 2 State

10058

1

1

Load Circuit 3 State

10059

1

1

Load Circuit 4 State

10060

1

1

Load Circuit 5 State

10061

1

1

Load Circuit 6 State

10062

1

1

Load Circuit 7 State

10063

1

1

Load Circuit 8 State

10064

1

1

Load Circuit 9 State

10065

1

1

Load Circuit 10 State

10066

1

1

Load Circuit 11 State

10067

1

1

Load Circuit 12 State

10068

1

1

Load Circuit 13 State

10069

1

1

Load Circuit 14 State

10070

1

1

Load Circuit 15 State

10071

1

1

Load Circuit 16 State

10072

1

1

Load On Inverter

10073

1

1

Bypass Active

10074

1

1

Buck On

10076

1

1

Replace Battery

10081

1

1

Battery Under Test

10082

1

1

Load On Battery

10128

1

1

Low Battery -
Shutdown Imminent

10152

1

1

Output Overload

10154

1

1

Over Temperature
Warning

10171

1

1

Battery Over
Temperature CB Trip

10172

1

1

Input Power Supply
Fail

10186

1

1

Input Over Voltage

10187

1

1

Input Under Voltage

10188

1

1

Bad Input Frequency

10190

1

1

Bypass Input
Voltage/Frequency
Fault

10202

1

1

Output Under Voltage

10218

1

1

Output Over Voltage

10219

1

1