Liebert Monitoring Group –Development
16
Hardware
Load On Battery
10128
1
1
Output Off Pending
10151
1
1
Low Battery - Shutdown
Imminent
10152
1
1
Output Overload
10154
1
1
Over Temperature
Warning
10171
1
1
Input Power Supply Fail
10186
1
1
Input Over Voltage
10187
1
1
Input Under Voltage
10188
1
1
Input BrownOut
10189
1
1
Bad Input Frequency
10190
1
1
Output Under Voltage
10218
1
1
Output Over Voltage
10219
1
1
Charger Failed
10234
1
1
Battery Under Voltage
10241
1
1
Battery Over Voltage
10242
1
1
Data Point
Input Register Holding Register # of Reg. Scale Notes / Units
Number Of Input Lines
30004
40004
1
1
Bits 12 - 15
Number Of Output
Lines
30004
40004
1
1
Bits 8 - 11
Number Of SubModules
30009
40009
1
1
Load Circuit Present
30013 40013 1
There are 16 possible
Load Circuits. So each
bit represents 1 load
circuit. Load Circuit 1 is
bit 0, Load Circuit 2 is bit
1 and so on. If the bit is
1 then the Load Circuit
is supported.
Nominal Power Rating
30021
40021
2
1
VA
Nominal Input Voltage
30027 40027 1
1
V
Nominal Output Voltage
30028
40028
1
1
V
Nominal Input Current
30030 40030 1
1
A
Nominal Input
Frequency
30031
40031
1
10 Hz
Nominal Output
Frequency 30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
Nominal Battery Voltage
30034 40034 1
1
V
Nominal Battery
Capacity
30037
40037
1
1
minutes
Nominal Battery Float
Voltage 30038
40038
1
1
V
Auto Restart Delay
30051
40051
1
1
seconds
Device Low Battery
Time
30053 40053 1
1
min