beautypg.com

3 table 1-2. general specifications (continued) – KEPCO HSP Series Operator Manual User Manual

Page 9

background image

HSPSERIES OPR 050614

1-3

TABLE 1-2. GENERAL SPECIFICATIONS (Continued)

FIGURE 1-2. HSP (ALL), NOMINAL MAINS VOLTAGE:

TEMPERATURE DERATING,

FIGURE 1-3. HSP 1500W, LOW MAINS VOLTAGE:

TEMPERATURE, POWER DERATING

CHARACTERISTIC

REQUIREMENT

SIGNAL AND CONTROL

Remote Error Sensing

3.3V & 5V Models

0.25V per wire

All other Models

0.8V per wire

Remote On/Off Control

Isolated TTL-compatible signal; either logic
high or logic low will disable output.

Load Sharing

Within 5% of load when connected via load
sharing wire (see PAR. 2.7.6).

Load Monitor

0-5V analog signal proportional to output
load current; 5V at 100% of rated load.

Status Flags

(Form C dry relay contacts)

(see PAR. 3.14)

(See Notes 5 and 7.)

POWER

Indicates low source
voltage; signal
asserted a minimum of
5 msec prior to loss of
output voltage.

OUTPUT

Indicates HSP Power
Supply in normal
operating mode.

OVERTEMP

Indicates HSP Power
Supply in overtemper-
ature shutdown.

FAN FAIL

Indicates failure of
internal cooling fan.

Status Indicators

(front Panel LEDs)

(See Note 5.)

POWER

Green; lit when source
voltage is above
minimum limit to
support output voltage.

DCFAIL

Red; lit when output is
outside normal voltage
regulation limits

OVERTEMP

Yellow; lit when over-
temperature protec-
tion is activated.

FAN FAIL

Red; lit when fan
failure latch is
activated.

Front Panel

Test Points

Monitors output voltage and current limit set
points; allows each HSP Power Supply to
be set while operating in any configuration,
including redundant mode.

Front Panel Meter

Accuracy

(M Option only)

Voltmeter: ±1%
Ammeter: ±10% from 25 to 100% of rated
output current.

CHARACTERISTIC

REQUIREMENT

SIGNAL AND CONTROL (CONTINUED)

Auxiliary Voltage

(Isolated)

4.75-5.25V d-c output, 0 - 100mA, parallelable,
output isolated (500 V d-c), Input isolated
(SELV) (See Operating Instructions, PAR. 3.11).

Voltage Set

Programming

Mode selected by

internal switches

(See Note 6.)

(See PAR. 3.3.)

Internal

Multiturn pot

External 1 Resistance: 0-50K

External 2 0-10V, 500

A max

Current Limit

Programming

Internal

Multiturn pot

External

0-10V, 500

A max

ENVIRONMENT

Temperature Range

Operating

0 to 50° C: rated load (50 ° C to 71°
C: derate by 2.5%/° C, Figure 1-2)
For 1500W at lower mains voltage:
see Figure 1-3 and Note 1:

Storage

–40 to +85

o

C

Cooling

Internal d-c fan (inlet, exhaust as indicated in
Figure 1-4).

Humidity

0-95% RH (non-condensing), Operating and
Storage.

Shock

Non-operating, 20g, 11msec 50%, half sine,
3 axes, 3 shocks each axis

Vibration

5-10Hz

10mm, double amplitude

10-55Hz

2g

Altitude

Sea level to 10,000 feet

PHYSICAL

Dimensions

See Figure 1-4.

Weight

16 lbs. (7.3Kg)

Source

Connections

3-pin power entry module (compatible with IEC
320/C19 molded line cord plug.

Load

Connection

Two bus bars (+ and –) 1.0 x 0.125 inch, copper
w/bright nickel finish

Signal Connection

37-pin D-subminiature connector (male)

NOTES 5: Status indicators and status flags are isolated and operate

independently, although driven by the same detector circuit.

6: The POWER/DCFAIL fault detector window tracks pro-

grammed output voltage, however, the overvoltage protection
trip point remains unaffected.

7. Form C contacts: rated from 30V d-c/1A to 60V d-c/0.3A.