STATUS INDICATORS AND STATUS FLAGS

HSP power supplies provide both visual and electrical indication of the status of various critical
functions including source power status, output status, fan status and overtemperature condi-
tion; both visual and signal indicators are provided. Visual indication is provided via the four LED
indicators located on the front panel (see Figure 2-1). Signal indication is obtained via four sets
of Form C dry relay contacts accessed via the I/O connector; all three contacts are provided to
the user, permitting the selection of either normally-open (NO), normally-closed (NC) or both for
any application (refer to Table 2-1). The definition of “normal” in this instance refers to the status
of the contacts when the HSP is powered and operating normally (no fault); status flag outputs
remain valid even when source power is removed. These relay contacts are SELV and are iso-
lated from each other and from the output by 100V d-c to permit flexibility in application. A
description of the function of each status signal follows. Table 3-1 indicates the condition of sta-
tus flags and indicators for normal, fault, and no power conditions.

TABLE 3-1. STATUS INDICATORS AND FLAGS

CONDITION

SIGNAL/INDICATOR

STATUS **

NORMAL *

FAULT DETECTED

NO POWER

APPLIED

SOURCE

POWER

STATUS

POWER INDICATOR

ON (GREEN)

OFF

OFF

SOURCE POWER STATUS NC

CLOSED

OPEN

OPEN

SOURCE POWER STATUS NO

OPEN

CLOSED

CLOSED

OUTPUT

STATUS

DC FAIL INDICATOR

OFF

ON (RED)

OFF

OUTPUT STATUS NC

CLOSED

OPEN

OPEN

OUTPUT STATUS NO

OPEN

CLOSED

CLOSED

FAN

STATUS

FANFAIL INDICATOR

OFF

ON (RED)

OFF

FAN STATUS NC

CLOSED

OPEN

CLOSED

FAN STATUS NO

OPEN

CLOSED

OPEN

OVERTEMPERATURE

STATUS

OVERTEMP INDICATOR

OFF

ON (AMBER)

OFF

OVERTEMP STATUS NC

CLOSED

OPEN

CLOSED

OVERTEMP STATUS NO

OPEN

CLOSED

OPEN

*

NORMAL IS DEFINED AS THE HSP POWERED AND OPERATING WITH NO FAULTS (SOURCE POWER WITHIN
SPECIFICATIONS, OUTPUT POWER WITHIN RATED LIMITS, FAN OPERATING, AND NO OVERTEMPERATURE CON-
DITION SENSED).

** CLOSED AND OPEN ARE REFERENCED TO THE ASSOCIATED STATUS COMMON TERMINATION.

NOTE:UPON INITIAL TURN-ON, FAN AND OVERTEMPERATURE STATUS LINES WILL BE IN “NORMAL” CONDITION

UNLESS A FAULT CONDITION IS SENSED.